Engineering data

REMARK: Do not use for construction. Refer to factory certified dimensions & weights. This page includes data current at time of publication, which should be reconfirmed at the time of purchase. In the interest of product improvement, specifications, weights and dimensions are subject to change without notice.

General notes

1. Dry Cooler capacaties are tested according to EN 1048.
2. Ratings shown are for clean tubes with 34% ethylene glycol solution by volume, 40°C in and 35°C out, 25°C ambient air temperature.
3. Sound Pressure Levels (LpA) are measured in the horizontal plane at a distance of 10 m from the connection end of the unit, under free field conditions.

Last update: 24/05/2019

DFCV L80XX

DFCV_engineering_data

Model Nr. of Fans Nominal Capacity (kW) Air Flow (m³/s) Cooling Agent l/s Δp kPa Tube Internal Volume (dm³) Surface (m²) Connections Ship. Weight(kg) LpA dB(A) Dimensions (mm)
Δ/ϒΔ/ϒΔ/ϒΔ/ϒΔ/ϒLWH
L8022-H413B 4 (2+2) 236/202 18,0/14,7 12,4/10,7 74/56 121 992 4 x ND80 916 60/57 2517 2400 2664
L8022-H416B 4 (2+2) 240/207 18,8/15,4 12,6/21,2 27/21 191 890 4 x ND80 1046 60/57 2517 2400 2664
L8023-L413B 6 (3+3) 353/302 27,0/22,1 18,6/15,9 74/56 182 1487 4 x ND80 1283 61/58 3617 2400 2664
L8023-L416B 6 (3+3) 357/310 28,2/23,1 18,9/16,4 28/22 287 1335 4 x ND80 1462 61/58 3617 2400 2664
L8024-S413B 8 (4+4) 472/405 36,0/29,5 24,9/21,4 80/60 243 1983 4 x ND80 1677 62/59 4717 2400 2664
L8024-S416B 8 (4+4) 480/415 37,6/30,8 25,3/21,9 33/25 382 1779 4 x ND80 1924 62/59 4717 2400 2664
L8025-S413B 10 (5+5) 601/513 45,0/36,9 31,7/27,1 124/94 303 2479 8 x ND80 2070 63/60 5817 2400 2664
L8025-S416B 10 (5+5) 615/523 47,0/38,5 32,5/27,6 46/34 478 2224 8 x ND80 2387 63/60 5817 2400 2664
L8026-D413B 12 (6+6) 686/587 54,0/44,2 36,3/31,0 35/26 364 2975 8 x ND80 2464 63/60 6917 2400 2664
L8026-D416B 12 (6+6) 706/608 56,4/46,2 37,3/32,1 15-Nov 574 2669 8 x ND80 2822 63/60 6917 2400 2664